Online 3:3 Transformer less UPS

The 3:3 transformer‑less UPS combines compact design with advanced functionality, delivering an output power factor of up to 1 and on‑line efficiency of 95.6% for reliable performance with minimal energy loss. Capable of handling inductive and capacitive loads without derating, it supports parallel operation of up to six units for scalability. Its modular design allows easy front‑side maintenance, while fan redundancy and speed control enhance reliability. With on‑line double conversion and high‑frequency technology, it covers capacities from 10 to 1000 KVA. User‑friendly features include one‑click upgrades via upper computer software and comprehensive circuit breaker configurations for seamless control of mains, bypass, maintenance, and output, making it an efficient and flexible solution for critical environments.

 

Choose your Model

Technical Specification

POWERON Three Phase 10KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 10000VA/10000W

 
Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range40% load:138~485Vac; Full load:342~485Vac
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)Less than 3%
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequency50 Hz or 60 Hz (setting value)
Harmonic distortion (THD)< 2% linear load and < 4% non-linear load
Power Factor1.0
Voltage Regulation± 1%
Output WaveformPure Sine wave
Efficiencyup to 95.6%
Overload Operation110% for 60 min; 125% for 10 min; 150 for 1 min
Output frequency synchronizationsynchronize with input; when input frequency < ±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz.
Environment 
Operating Temperature0°C~40°C
System Features 
Communication interfaceUSB, RS485, Parallel, Relay card(optional), SNMP(optional), Battery temperature sensor(optional), dry contact(EPO_NC, EPO_NO, BAT_SW, BACKFEED or BAT_DRV)
Battery 
Battery Voltage

Optional Voltage: ±180/192/204/216/228/

240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/

44/46/48/50pcs optional);

360Vdc~600Vdc (30~50 pcs,

36 pcs define, 36~50 pcs

no power derating; 32~

34 pcs output power

factor 0.9; 30 pcs output

power factor 0.8;)

Charging current (Max)15
Physical 
Weight129 Kg
Height868 mm
Width250 mm
Length900 mm

 

Technical Specification

POWERON Three Phase 15KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 15000VA/15000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range40% load:138~485Vac; Full load:342~485Vac
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)Less than 3%
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequency50 Hz or 60 Hz (setting value)
Harmonic distortion (THD)< 2% linear load and < 4% non-linear load
Power Factor1.0
Voltage Regulation± 1%
Output WaveformPure Sine wave
Overload Operation110% for 60 min; 125% for 10 min; 150 for 1 min
Output frequency synchronizationsynchronize with input; when input frequency < ±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz.
Efficiencyup to 95.6%
Environment 
Operating Temperature0°C ~ 40°C
System Features 
Communication interfaceUSB, RS485, Parallel, Relay card(optional), SNMP(optional), Battery temperature sensor(optional), dry contact(EPO_NC, EPO_NO, BAT_SW, BACKFEED or BAT_DRV)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)15
Physical 
Weight186 Kg
Height868 mm
Width250 mm
Length900 mm

Technical Specification

POWERON Three Phase 20KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 20000VA/20000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range40% load:138~485Vac; Full load:342~485Vac
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)Less than 3%
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequency50 Hz or 60 Hz (setting value)
Harmonic distortion (THD)< 2% linear load and < 4% non-linear load
Power Factor1.0
Voltage Regulation± 1%
Output WaveformPure Sine wave
Efficiencyup to 95.6%
Overload Operation110% for 60 min; 125% for 10 min; 150 for 1 min
Output frequency synchronizationsynchronize with input; when input frequency < ±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz.
Environment 
Operating Temperature0℃~40℃
System Features 
Communication interfaceUSB, RS485, Parallel, Relay card(optional), SNMP(optional), Battery temperature sensor(optional), dry contact(EPO_NC, EPO_NO, BAT_SW, BACKFEED or BAT_DRV)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)15
Physical 
Weight187 Kg
Height868 mm
Width250 mm
Length900 mm

Technical Specification

POWERON Three Phase 30KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 30000VA/30000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range40% load:138~485Vac; Full load:342~485Vac
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)Less than 3%
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequency50 Hz or 60 Hz (setting value)
Harmonic distortion (THD)< 2% linear load and < 4% non-linear load
Power Factor1.0
Voltage Regulation± 1%
Output WaveformPure Sine wave
Efficiencyup to 95.6%
Overload Operation110% for 60 min; 125% for 10 min; 150 for 1 min
Output frequency synchronizationsynchronize with input; when input frequency < ±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz.
Environment 
Operating Temperature0°C~40°C
System Features 
Communication interfaceUSB, RS485, Parallel, Relay card(optional), SNMP(optional), Battery temperature sensor(optional), dry contact(EPO_NC, EPO_NO, BAT_SW, BACKFEED or BAT_DRV)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)15
Physical 
Weight236 Kg
Height868 mm
Width250 mm
Length900 mm

Technical Specification

POWERON Three Phase 40KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 40000VA/40000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range40% load:138~485Vac; Full load:342~485Vac
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)Less than 3%
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequency50 Hz or 60 Hz (setting value)
Harmonic distortion (THD)< 2% linear load and < 4% non-linear load
Power Factor1.0
Voltage Regulation± 1%
Output WaveformPure Sine wave
Overload Operation110% for 60 min; 125% for 10 min; 150 for 1 min
Output frequency synchronizationsynchronize with input; when input frequency < ±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz.
Efficiencyup to 95.6%
Environment 
Operating Temperature0°C~40°C
System Features 
Communication interfaceUSB, RS485, Parallel, Relay card(optional), SNMP(optional), Battery temperature sensor(optional), dry contact(EPO_NC, EPO_NO, BAT_SW, BACKFEED or BAT_DRV)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)15
Physical 
Weight239
Height868
Width250
Length890

Technical Specification

POWERON Three Phase 50KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 50000VA/50000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range40% load:138~485Vac; Full load:342~485Vac
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)Less than 3%
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequency50 Hz or 60 Hz (setting value)
Harmonic distortion (THD)< 2% linear load and < 4% non-linear load
Power Factor1.0
Voltage Regulation± 1%
Efficiencyup to 95.6%
Overload Operation110% for 60 min; 125% for 10 min; 150 for 1 min
Output frequency synchronizationsynchronize with input; when input frequency < ±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz.
Environment 
Operating Temperature0°C~40°C
System Features 
Communication interfaceUSB, RS485, Parallel, Relay card(optional), SNMP(optional), Battery temperature sensor(optional), dry contact(EPO_NC, EPO_NO, BAT_SW, BACKFEED or BAT_DRV)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)15
Physical 
Weight80
Height868
Width250
Length828

Technical Specification

POWERON Three Phase 60KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 60000VA/60000W

 
Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range40% load:138~485Vac; Full load:342~485Vac
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)Less than 3%
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequency50 Hz or 60 Hz (setting value)
Harmonic distortion (THD)< 2% linear load and < 4% non-linear load
Power Factor1.0
Voltage Regulation± 1%
Output WaveformPure Sine wave
Efficiencyup to 95.6%
Overload Operation110% for 60 min; 125% for 10 min; 150 for 1 min
Output frequency synchronizationsynchronize with input; when input frequency < ±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz.
Environment 
Operating Temperature0°C~40°C
System Features 
Communication interfaceUSB, RS485, Parallel, Relay card(optional), SNMP(optional), Battery temperature sensor(optional), dry contact(EPO_NC, EPO_NO, BAT_SW, BACKFEED or BAT_DRV)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)15
Physical 
Weight83
Height868
Width250
Length890

Technical Specification

POWERON Three Phase 80KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 80000VA/80000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range40% load:138~485Vac; Full load:342~485Vac
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)Less than 3%
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequency50 Hz or 60 Hz (setting value)
Harmonic distortion (THD)< 2% linear load and < 4% non-linear load
Power Factor1.0
Voltage Regulation± 1%
Output WaveformPure Sine wave
Efficiencyup to 95.6%
Overload Operation110% for 60 min; 125% for 10 min; 150 for 1 min
Output frequency synchronizationsynchronize with input; when input frequency < ±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz.
Environment 
Operating Temperature0°C~40°C
System Features 
Communication interfaceUSB, RS485, Parallel, Relay card(optional), SNMP(optional), Battery temperature sensor(optional), dry contact(EPO_NC, EPO_NO, BAT_SW, BACKFEED or BAT_DRV)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)15
Physical 
Weight144
Height1200
Width442
Length850
 

Technical Specification

POWERON Three Phase 100KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 100000VA/100000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range40% load:138~485Vac; Full load:342~485Vac
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)Less than 3%
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequency50 Hz or 60 Hz (setting value)
Efficiencyup to 95.6%
Harmonic distortion (THD)< 2% linear load and < 4% non-linear load
Power Factor1.0
Output WaveformPure Sine wave
Efficiencyup to 95.6%
Overload Operation110% for 60 min; 125% for 10 min; 150 for 1 min
Output frequency synchronizationsynchronize with input; when input frequency < ±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz.
Environment 
Operating Temperature0°C~40°C
System Features 
Communication interfaceUSB, RS485, Parallel, Relay card(optional), SNMP(optional), Battery temperature sensor(optional), dry contact(EPO_NC, EPO_NO, BAT_SW, BACKFEED or BAT_DRV)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)15
Physical 
Weight147
Height1200
Width442
Length850
 

Technical Specification

POWERON Three Phase 120KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 120000VA/120000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range40% load:138~485Vac; Full load:342~485Vac
Power Factor≥0.99
Harmonic distortion (THDi)Less than 3%
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequency50 Hz or 60 Hz (setting value)
Harmonic distortion (THD)< 2% linear load and < 4% non-linear load
Power Factor1.0
Output WaveformPure Sine wave
Efficiencyup to 95.6%
Overload Operation110% for 60 min; 125% for 10 min; 150 for 1 min
Output frequency synchronizationsynchronize with input; when input frequency < ±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz.
Environment 
Operating Temperature0°C~40°C
System Features 
Communication interfaceUSB, RS485, Parallel, Relay card(optional), SNMP(optional), Battery temperature sensor(optional), dry contact(EPO_NC, EPO_NO, BAT_SW, BACKFEED or BAT_DRV)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)15
Physical 
Weight152
Height1200
Width442
Length850
 

Technical Specification

POWERON Three Phase 160KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 160000VA/160000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range138~305Vac for 40% load; 305~485Vac for 100% load
Power Factor≥0.99
Harmonic distortion (THDi)≤ 3%(100% linear load)
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequency(50/60±0.1%)Hz
Harmonic distortion (THD)≤ 1% with linear load ≤ 3% with non linear load
Power Factor1.0
Voltage Regulation± 1%
Efficiencyup to 95.6%
Overload Operation≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Environment 
Operating Temperature0°C~40°C
Storage Temperature– 25°C ~ 55°C
Relative Humidity0 ~ 95% (non condensing)
Noise level< 65dB
System Features 
Communication interfaceRS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)45
Physical 
Weight200
Height1200
Width442
Length850
 

Technical Specification

POWERON Three Phase 200KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 200000VA/200000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range138~305Vac for 40% load; 305~485Vac for 100% load
Power Factor≥0.99
Harmonic distortion (THDi)≤ 3%(100% linear load)
Operating frequency range40Hz-70Hz
Bypass voltage rangeMax. voltage: 220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Generator inputSupport
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequencySynchronize with input, when the input frequency > ±10% (±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) / (50/60±0.1%)Hz
Harmonic distortion (THD)≤ 1% with linear load ≤ 3% with non linear load
Power Factor1.0
Voltage Regulation± 1%
Efficiencyup to 96%
Overload Operation≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Environment 
Operating Temperature0°C~40°C
Storage Temperature– 25°C ~ 55°C
Relative Humidity0 ~ 95% (non condensing)
Noise level< 65dB
System Features 
Communication interfaceRS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
Transfer timeUtility to Battery : 0ms; Utility to Bypass: 0ms
Overload≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)80
Physical 
Weight342
Height1600
Width600
Length850
 

Technical Specification

POWERON Three Phase 250KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 250000VA/250000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range138~305Vac for 40% load; 305~485Vac for 100% load
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)≤ 3%(100% linear load)
Bypass frequency rangeMax. voltage: 220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Generator inputSupport
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequencySynchronize with input, when the input frequency > ±10% (±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) / (50/60±0.1%)Hz
Harmonic distortion (THD)≤ 1% with linear load ≤ 3% with non linear load
Power Factor1.0
Voltage Regulation± 1%
Efficiencyup to 96%
Overload Operation≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Environment 
Operating Temperature0°C~40°C
Storage Temperature– 25°C ~ 55°C
Relative Humidity0 ~ 95% (non condensing)
Noise level< 65dB
System Features 
Transfer timeUtility to Battery : 0ms; Utility to Bypass: 0ms
Overload≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Communication interfaceRS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)100
Physical 
Weight385
Height1600
Width600
Length850
 

Technical Specification

POWERON Three Phase 300KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 300000VA/300000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range138~305Vac for 40% load; 305~485Vac for 100% load
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)≤ 3%(100% linear load)
Bypass frequency rangeMax. voltage: 220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Generator inputSupport
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequencySynchronize with input, when the input frequency > ±10% (±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) / (50/60±0.1%)Hz
Harmonic distortion (THD)≤ 1% with linear load ≤ 3% with non linear load
Power Factor1.0
Voltage Regulation± 1%
Efficiencyup to 96%
Overload Operation≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Environment 
Operating Temperature0°C~40°C
Storage Temperature– 25°C ~ 55°C
Relative Humidity0 ~ 95% (non condensing)
Noise level< 68dB
System Features 
Transfer timeUtility to Battery : 0ms; Utility to Bypass: 0ms
Overload≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Communication interfaceRS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)100
Physical 
Weight401
Height1600
Width600
Length850
 

Technical Specification

POWERON Three Phase 400KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 400000VA/400000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range138~305Vac for 40% load; 305~485Vac for 100% load
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)≤ 3%(100% linear load)
Bypass frequency rangeMax. voltage: 220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Generator inputSupport
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequencySynchronize with input, when the input frequency > ±10% (±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) / (50/60±0.1%)Hz
Efficiencyup to 96%
Harmonic distortion (THD)≤ 1% with linear load ≤ 3% with non linear load
Power Factor1.0
Voltage Regulation± 1%
Overload Operation≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Environment 
Operating Temperature0°C~40°C
Storage Temperature– 25°C ~ 55°C
Relative Humidity0 ~ 95% (non condensing)
Altitude< 68dB
System Features 
Transfer timeUtility to Battery : 0ms; Utility to Bypass: 0ms
Overload≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Communication interfaceRS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)140
Physical 
Weight542
Height2000
Width600
Length850
 

Technical Specification

POWERON Three Phase 500KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 500000VA/500000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range138~305Vac for 40% load; 305~485Vac for 100% load
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)≤ 3%(100% linear load)
Bypass frequency rangeMax. voltage: 220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Generator inputSupport
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequencySynchronize with input, when the input frequency > ±10% (±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) / (50/60±0.1%)Hz
Harmonic distortion (THD)≤ 1% with linear load ≤ 3% with non linear load
Power Factor1.0
Voltage Regulation± 1%
Efficiencyup to 96%
Overload Operation≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Environment 
Operating Temperature0°C~40°C
Storage Temperature– 25°C ~ 55°C
Relative Humidity0 ~ 95% (non condensing)
Noise level< 70dB
System Features 
Transfer timeUtility to Battery : 0ms; Utility to Bypass: 0ms
Overload≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Communication interfaceRS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)180
Physical 
Weight800
Height2000
Width1200
Length850
 

Technical Specification

POWERON Three Phase 600KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 600000VA/600000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range138~305Vac for 40% load; 305~485Vac for 100% load
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)≤ 3%(100% linear load)
Bypass frequency rangeMax. voltage: 220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Generator inputSupport
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequencySynchronize with input, when the input frequency > ±10% (±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) / (50/60±0.1%)Hz
Harmonic distortion (THD)≤ 1% with linear load ≤ 3% with non linear load
Power Factor1.0
Efficiencyup to 96%
Overload Operation≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Environment 
Operating Temperature0°C~40°C
Storage Temperature– 25°C ~ 55°C
Relative Humidity0 ~ 95% (non condensing)
Noise level< 70dB
System Features 
Transfer timeUtility to Battery : 0ms; Utility to Bypass: 0ms
Overload≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Communication interfaceRS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)200
Physical 
Weight890
Height2000
Width1200
Length850
 

Technical Specification

POWERON Three Phase 800KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 800000VA/800000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range138~305Vac for 40% load; 305~485Vac for 100% load
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)≤ 3%(100% linear load)
Bypass frequency rangeMax. voltage: 220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Generator inputSupport
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequencySynchronize with input, when the input frequency > ±10% (±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) / (50/60±0.1%)Hz
Harmonic distortion (THD)≤ 1% with linear load ≤ 3% with non linear load
Power Factor1.0
Voltage Regulation± 1%
Efficiencyup to 96%
Overload Operation≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Environment 
Operating Temperature0°C~40°C
Storage Temperature– 25°C ~ 55°C
Relative Humidity0 ~ 95% (non condensing)
Noise level< 73dB
System Features 
Transfer timeUtility to Battery : 0ms; Utility to Bypass: 0ms
Overload≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Communication interfaceRS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)280
Physical 
Weight1450
Height2000
Width2000
Length850
 

Technical Specification

POWERON Three Phase 1000KVA Online Double Conversion UPS with 1pf, Semi Modular Concept Design

Capacity (VA/Watts): 1000000VA/1000000W

Input 
Nominal voltage380/400/415; 3Ph+N+PE
Operating voltage range138~305Vac for 40% load; 305~485Vac for 100% load
Operating frequency range40Hz-70Hz
Power Factor≥0.99
Harmonic distortion (THDi)≤ 3%(100% linear load)
Bypass frequency rangeMax. voltage: 220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Generator inputSupport
Output 
Output voltage380/400/415; 3Ph+N+PE
Output frequencySynchronize with input, when the input frequency > ±10% (±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) / (50/60±0.1%)Hz
Harmonic distortion (THD)≤ 1% with linear load ≤ 3% with non linear load
Power Factor1.0
Voltage Regulation± 1%
Efficiencyup to 96%
Overload Operation≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Environment 
Operating Temperature0°C~40°C
Storage Temperature– 25°C ~ 55°C
Relative Humidity0 ~ 95% (non condensing)
Noise level< 75 dB
System Features 
Transfer timeUtility to Battery : 0ms; Utility to Bypass: 0ms
Overload≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. 135% overload for long term; >1000% overload for 100 ms
Communication interfaceRS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
Battery 
Battery VoltageOptional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8;)
Charging current (Max)340
Physical 
Weight1600
Height2000
Width2000
Length850
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 95.6%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design ,easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 96%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design, easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 96%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software ( LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design, easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 96%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software (LCD excluded)
  • Completed CB configurations for mains ,bypass ,maintenance and output 
  • Modular-concept design, easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 96%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software (LCD excluded)
  • Completed CB configurations for mains, bypass, maintenance and output 
  • Modular-concept design, easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 96%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software (LCD excluded)
  • Completed CB configurations for mains, bypass, maintenance and output 
  • Modular-concept design, easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 96%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software (LCD excluded)
  • Completed CB configurations for mains, bypass, maintenance and output 
  • Modular-concept design, easily maintenance by replacing power modules from front side (no need side and rear maintenances) 
 

Features

  • Output PF up to 1
  • Parallel up to 6 units
  • On line efficiency up to 96%
  • Compact sizes with limited foot-prints
  • Fan redundancy design, speed Control
  • No derating for PF≥0.5 inductive load and capacitive load
  • On-line double conversion and high frequency UPS 10-1000KVA 
  • One-click upgradation by upper computer software (LCD excluded)
  • Completed CB configurations for mains, bypass, maintenance and output 
  • Modular-concept design, easily maintenance by replacing power modules from front side (no need side and rear maintenances) 

Online 3:1 Transformer less UPS

Online 3:3 Transformer based UPS

Servo Prime Series

Support Center

Our dedicated support team ensures 24/7 assistance, providing technical support, addressing queries, and receiving feedback at any time. We are just one call away.

Product Warranty

Register your Enerbyte Tech product today to activate your warranty coverage and ensure full manufacturer protection for your investment.

RMA Registration

Upgrading, refurbishing, or experiencing a fault? Register here for a Return Merchandise Authorization and our team will guide you through the repair or replacement process.

Extended Warranty

Extend the warranty period of your Enerbyte Tech product and enjoy long-term peace of mind. More coverage means more protection for your critical power systems.

Scroll to Top