Online 3:3 Transformer based UPS
The 3:3 transformer‑based UPS provides exceptional power protection with an integrated output isolation transformer that ensures complete electrical separation, shielding critical equipment from disturbances. Its double conversion on‑line design delivers a pure sine wave output with zero transfer time, making it ideal for sensitive applications. With a high input power factor of 0.98, it improves energy efficiency and reduces harmonic distortion, while full DSP control guarantees stable and reliable performance. N+X parallel redundancy enhances system reliability, intelligent battery management extends battery life, and comprehensive protection features safeguard equipment, ensuring long‑term stability and dependable operation.
Choose your Model
Technical Specification
GP339 Series 10KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 10000VA/9000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 2% ( Linear load) |
| Efficiency | >89% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 60dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min ,125%/10min ,150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | lEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 217Kg |
| Height | 1195 mm |
| Width | 570 mm |
| Length | 800 mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 10KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 10000VA/9000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 2% ( Linear load) |
| Efficiency | >89% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 60dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min ,125%/10min ,150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | lEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 217Kg |
| Height | 1195 mm |
| Width | 570 mm |
| Length | 800 mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 30KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 30000VA/27000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Efficiency | >91% |
| Harmonic distortion (THD) | < 2% ( Linear load) |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 60dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min ,125%/10min ,150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | lEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 316 Kg |
| Height | 1195 mm |
| Width | 570 mm |
| Length | 800 mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 40KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 40000VA/36000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 2% ( Linear load) |
| Efficiency | >91% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 65dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | lEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 330kg |
| Height | 1195mm |
| Width | 570mm |
| Length | 800mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 60KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 60000VA/54000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 2% ( Linear load) |
| Efficiency | >92% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 65dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | lEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 483kg |
| Height | 1600mm |
| Width | 760mm |
| Length | 880mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 80KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 80000VA/72000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Efficiency | >92% |
| Harmonic distortion (THD) | < 2% ( Linear load) |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 60dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | lEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 568kg |
| Height | 1600mm |
| Width | 760mm |
| Length | 880mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 100KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 100000VA/90000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 3% ( Linear load) |
| Efficiency | >92% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 65dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | IEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Width | 800kg |
| Length | 1600mm |
| Packing Width | 805mm |
| Packing depth | 1160mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 120KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 120000VA/108000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (±5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 3% ( Linear load) |
| Efficiency | >92% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 65dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | IEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 903kg |
| Height | 1600mm |
| Width | 805mm |
| Length | 1160mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 160KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 160000VA/144000W
| Input | |
|---|---|
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 3% ( Linear load) |
| Efficiency | >92% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 65dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | IEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 1219kg |
| Height | 1900mm |
| Width | 945mm |
| Length | 1400mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 200KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 200000VA/180000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 3% ( Linear load) |
| Efficiency | >92.5% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 65dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | Input, Inverter, Bypass, Battery, Output, Status |
| EMC | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Physical | |
|---|---|
| Weight | 1425kg |
| Height | 1900mm |
| Width | 945mm |
| Length | 1400mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 300KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 300000VA/270000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 3% ( Linear load) |
| Efficiency | >93% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 70dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | IEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 1800kg |
| Height | 1900mm |
| Width | 1040mm |
| Length | 1640mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 400KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 400000VA/360000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.98(with filter) |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 3% ( Linear load) |
| Efficiency | >94% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 70dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 384Vdc |
| Standard | |
|---|---|
| Safety | IEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 2050kg |
| Height | 1900mm |
| Width | 1040mm |
| Length | 1640mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 500KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 500000VA/450000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.85 |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 3% ( Linear load) |
| Efficiency | >95% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 70dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 480Vdc |
| Standard | |
|---|---|
| Safety | IEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 3700kg |
| Height | 1900mm |
| Width | 1040mm |
| Length | 2800mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 600KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 600000VA/540000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.85 |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 3% ( Linear load) |
| Efficiency | >95% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 70dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 480Vdc |
| Standard | |
|---|---|
| Safety | IEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 4500kg |
| Height | 1900mm |
| Width | 1040mm |
| Length | 2800mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series
VRLA AGM
Technical Specification
GP339 Series 800KVA UPS Three Phase Online Double Conversion UPS with integrated Output Transformer, Additional Input Harmonic Filtering, Semi Industrial Grade
Capacity (VA/Watts): 800000VA/720000W
| Input | |
|---|---|
| Operating voltage range | 380/400/415Vac (380~25%, 415+20% ), (3Ph+N+PE) |
| Operating frequency range | 50/60Hz (± 5Hz) |
| Power Factor | ≥ 0.85 |
| Output | |
|---|---|
| Output voltage | 380/400/415VAC ( ± 1%) |
| Output frequency | 50/60Hz (±0.05%) |
| Crest factor | 3:1 (Max.) |
| Harmonic distortion (THD) | < 3% ( Linear load) |
| Efficiency | >96% |
| Environment | |
|---|---|
| Operating Temperature | 0 ~ 40°C |
| Storage Temperature | -25°C ~ 55°C |
| Relative Humidity | 0 ~ 95% (non condensing) |
| Altitude | < 1500m |
| Noise level | < 70dB |
| System Features | |
|---|---|
| Transfer time | 0ms (Line mode —> Battery mode) |
| Overload | 110%/60min, 125%/10min, 150%/1min |
| Communication interface | Dry contact, RS232, RS485, SNMP card (Optional) |
| Indicators | |
|---|---|
| LED Display(LED version) | Input, Inverter, Bypass, Battery, Output, Status |
| LCD Display(LCD version) | l/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record |
| Battery | |
|---|---|
| Battery Voltage | 480Vdc |
| Standard | |
|---|---|
| Safety | IEC/EN62040-1;lEC/EN60950-1 |
| EMC | IEC/EN52040-2;IEC51000-4-2;IEC61000-4-3;IEC61000-4-4; IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
| Physical | |
|---|---|
| Weight | 6400kg |
| Height | 1950mm |
| Width | 1100mm |
| Length | 3900mm |
Features
- Double conversion on-line design ensures pure sine wave output with frequency tracking, phase lock, voltage regulation, and noise suppression.
- Zero transfer time meets high precision power requirements.
- Input power factor of 0.98 enhances energy efficiency and reduces harmonic pollution.
- Full DSP control offers stable, reliable performance.
- High output power factor of 0.9 increases load capacity and investment savings.
- Wide AC input voltage range (380/400/415Vac ±25%) extends battery life.
- Wide input frequency (45-65Hz) ensures stable generator connection.
- Intelligent battery management (ABM) extends battery life and reduces maintenance.
- Advanced charging technology maximizes battery activation, saving time and extending life.
- Predictive battery discharge system alerts users with discharge time estimates.
- Regular battery self-tests detect problems early.
- Flexible battery voltage range (320-490Vdc) for varied configurations.
- N+X parallel redundancy supports up to 6 units for critical loads.
- Simple parallel function with easy cable connections.
- Non-fixed master-slave system ensures automatic load transfer in case of inverter failure.
- Strong overload capacity: 110% for 60 min, 125% for 10 min, 150% for 1 min.
- Generator compatibility with inrush current reduction for smooth startup.
- LBS synchronization keeps outputs of independent UPS systems aligned.
- Comprehensive protections against input/output faults, overloads, over-temperature, and more.
- Bypass function ensures continuous power during overload or UPS failure.
- EPO button for emergency shutdown, designed with concave cover to prevent misuse.
- User-friendly network management with English LCD and real-time communication via RS232, SNMP adapter.
Online Modular VRLA compatible UPS
Servo Prime Series